High Voltage Transmission Lines

Our Testing & Diagnostic Solutions

We provide comprehensive testing, diagnostic, and condition assessment services in compliance with relevant IEC, IEEE, and ASTM standards, ensuring the reliability, safety, and extended service life of critical electrical assets across transmission and distribution networks.

Our primary expertise lies in Partial Discharge (PD) diagnostics and advanced insulation assessment, supporting condition-based and risk-based maintenance strategies for utilities, EPCs, and industrial clients.

Scroll to Explore

Our Solutions

Comprehensive diagnostic services for critical electrical assets

Transformer Offline Diagnostic Services

Sweep Frequency Response Analysis (SFRA)

Detects winding deformation, core displacement, and mechanical movement caused by short-circuits, transportation, or seismic events.

IEC 60076-18IEEE C57.149

Turns Ratio (TTR) Measurement

Verifies winding ratio accuracy and identifies shorted, open, or incorrectly connected turns.

IEC 60076-1IEEE C57.12.90

Insulation Resistance (IR) & Polarization Index (PI)

Assesses insulation condition, moisture ingress, and contamination levels.

IEC 60076-1IEEE 43IEEE C57.152

Tan Delta & Capacitance Measurement

Evaluates insulation aging, dielectric losses, and moisture presence in windings and insulation systems.

IEC 60247IEC 60076-1IEEE C57.12.90

Transformer In-Service Diagnostics

Online Partial Discharge (PD) Measurement & Analysis

Comprehensive PD diagnostics using multiple sensor technologies including HFCT, Drain Valve Sensors, Acoustic Sensors, and RFI/UHF methods, enabling defect identification and trending without de-energizing the transformer.

IEC 60270IEC 62478IEEE C57.127IEEE C57.113

Dissolved Gas Analysis (DGA)

On-site and laboratory analysis of transformer insulating oil to detect thermal faults, electrical discharges, and insulation degradation.

IEC 60599 – Interpretation of DGA resultsIEC 60422 – Supervision and maintenance of insulating oilsIEEE C57.104 – Guide for interpretation of dissolved gas analysisASTM D3612 (A/B/C) – Gas chromatography analysis of dissolved gasesASTM D3613 – Sampling of insulating oil for gas analysisASTM D923 – Sampling of electrical insulating liquids

PD Trending & Condition Assessment Reports

Defect severity evaluation, condition grading, and maintenance recommendations aligned with international best practices.

Medium Voltage (MV) Switchgear

Partial Discharge (PD) Diagnostics

Detection of internal discharges, surface tracking, and corona in air-insulated compartments.

IEC 60270IEC 62478IEC 62271-1

Contact Resistance Measurement

Identifies high-resistance joints and deteriorated contacts.

IEC 62271-1IEC 62271-100IEEE C37.09

Insulation Resistance, Timing & Functional Tests

Confirms insulation integrity and mechanical performance of circuit breakers.

IEC 62271-1IEEE C37 series

Gas Insulated Switchgear (GIS)

GIS Partial Discharge (PD) Diagnostics

Detection and localization of internal insulation defects using UHF, HFCT, and acoustic methods.

IEC 60270IEC 62478IEC 62271-203

SF₆ Gas Analysis

Measurement of gas purity, moisture content, and decomposition by-products.

IEC 60376IEC 60480IEC 62271-1

Contact Resistance Measurement

Ensures reliable current paths and early detection of degradation.

IEC 62271-1IEC 62271-100

MV Cables

Partial Discharge (PD) Testing & Location

Identification and localization of insulation defects, joints, and terminations.

IEC 60270IEC 62478IEEE 400.3

VLF Withstand Testing

Verification of insulation integrity without excessive electrical stress.

IEC 60502-2IEC 60060-3IEEE 400.2

Tan Delta Measurement

Assessment of insulation aging, water treeing, and moisture ingress.

IEC 60247IEEE 400.2

HV & EHV Cables

Online & Offline Partial Discharge (PD) Testing

Accurate PD detection and localization along cable systems.

IEC 60270IEC 62478IEEE 400.3

Tan Delta & Capacitance Measurement

Evaluation of long-term insulation degradation and system uniformity.

IEC 60840IEC 62067

Cable Termination & Joint Diagnostics

Verification of installation quality at critical interfaces.

IEC 60840IEC 62067

Motor

Partial Discharge (PD) Measurement & Monitoring

Detection and analysis of insulation discharge activity in medium- and high-voltage stator windings.

IEC 60034-27IEC 60034-27-1IEEE 1434

Tan Delta & Capacitance Measurement

Assessment of resin-mica insulation systems for aging and degradation.

IEC 60034-27IEEE 286

Insulation Resistance & Polarization Index (PI)

Evaluation of moisture ingress, contamination, and overall insulation condition.

IEC 60034-1IEEE 43

Generator

Partial Discharge (PD) Measurement & Monitoring

Detection and analysis of insulation discharge activity in medium- and high-voltage stator windings.

IEC 60034-27IEC 60034-27-1IEEE 1434

Tan Delta & Capacitance Measurement

Assessment of resin-mica insulation systems for aging and degradation.

IEC 60034-27IEEE 286

Insulation Resistance & Polarization Index (PI)

Evaluation of moisture ingress, contamination, and overall insulation condition.

IEC 60034-1IEEE 43